Core Products: Terminal Blocks, Transfer Switches & Digital Panel Meters Supporting Electrical Categories | OEM/ODM | Project-Based Quotation
Catalogue
SENTOP industrial automatic transfer switch with integrated controller
Automatic Transfer Switch Manufacturer

Automatic Transfer Switches for Reliable Dual-Source Power Control

Select an ATS for utility-to-utility or utility-to-generator systems from the actual voltage, frequency, load current, poles, neutral arrangement, short-circuit coordination, controller logic and communication requirements. SENTOP supports model matching, drawings, samples and OEM bulk supply.

Explore ATS Range
PC and CB Class DirectionsMatch switching class to the protection strategy.
2P, 3P and 4P OptionsConfirm phase and neutral switching for the exact system.
Controller ConfigurationReview sensing, delays, generator contacts and communication.
Automatic Power Transfer

What does an automatic transfer switch do?

An automatic transfer switch monitors two power sources and transfers the connected load when the preferred source is unavailable or outside the configured limits. In a generator system, the controller may also issue a remote start signal, wait for the alternate source to stabilize and return the load after normal power is restored.

An ATS does not replace a complete power-system design. Source protection, grounding, neutral treatment, conductor sizing, fault-current coordination, generator controls and local electrical rules must be reviewed together with the exact switch model.

01

Monitor the preferred source

Check voltage, frequency, phase condition and controller-defined acceptance limits.

02

Confirm a persistent source problem

Use the configured delay to avoid an unnecessary transfer for a brief disturbance.

03

Prepare the alternate source

Verify the second utility source or start and stabilize the standby generator.

04

Transfer and later retransfer the load

Operate the switching mechanism in the approved sequence, then return after normal power is stable.

Automatic source monitoringDetect source conditions through the selected controller.
Controlled transitionTransfer according to model-specific switching and delay logic.
Manual operating provisionConfirm the exact model's maintenance and emergency operation method.
Project integrationCoordinate generator, BMS, fire input and status contacts as required.
Automatic Transfer Switch Class

Choose PC or CB class from the short-circuit strategy

The equipment class describes short-circuit capability and protection behavior. It is not simply a difference in enclosure shape or controller appearance.

PCTransfer switching equipment

PC Class ATS

PC class transfer switching equipment is capable of making and withstanding specified short-circuit currents but is not intended to break short-circuit currents. The installation requires correctly coordinated upstream short-circuit protection.

Review firstRated current, utilization category, Icw/Icm or conditional short-circuit data and upstream protective device.
Useful whenThe system protection design is separate from the transfer switching mechanism.
Do not assumeA high frame current alone proves suitable fault-current performance.
CBCircuit-breaker based TSE

CB Class ATS

CB class transfer switching equipment is intended to make, withstand and break short-circuit currents and is provided with overcurrent releases. Exact protection settings, breaking capacity and coordination remain model-specific.

Review firstRated current, trip unit or release, breaking capacity, settings, selectivity and source protection arrangement.
Useful whenThe project requires breaker-based switching and integrated overcurrent behavior.
Do not assumeEvery molded-case dual-power switch has the same class or protection function.

Selection reminder: Confirm the class, utilization category, short-circuit ratings, upstream protection and applicable IEC 60947-6-1 edition from the exact model datasheet and project specification.

Automatic Transfer Switch Product Range

Four ATS directions for different power systems

Use these product directions to narrow the range. Final selection must be confirmed from the exact model code, nameplate, datasheet and project requirements.

01Compact dual-power automatic transfer switch
Compact Power Transfer

Compact Automatic Transfer Switch

A compact switching direction for smaller distribution boards, equipment panels and limited installation spaces where automatic and manual transfer functions are required.

Confirm before orderingExact model, voltage, frequency, rated current, poles, rail or panel mounting, class, controller supply and terminal capacity.
02RP7S molded-case automatic transfer switch
Molded-Case ATS Direction

RP7S Automatic Transfer Switch

A molded-case automatic transfer direction for industrial and commercial distribution where current range, poles, short-circuit data and controller functions must be coordinated.

Confirm before orderingComplete RP7S code, frame and rated current, 3P or 4P, switching class, utilization category, controller and dimensions.
Product details
03RPQ8 automatic transfer switch with integrated controller
Controller-Equipped Industrial ATS

RPQ8 Automatic Transfer Switch

An industrial ATS direction with a visible controller interface for projects that need configurable source monitoring, delays, operating modes and status review.

Confirm before orderingExact RPQ8 code, rated voltage/current, poles, class, sensing thresholds, delay range, auxiliary contacts and documents.
Product details
04Generator automatic transfer switch for utility and standby generator systems
Utility and Generator System

Generator Automatic Transfer Switch

A generator-oriented ATS direction for monitoring the normal source, issuing generator start contacts, verifying standby power and controlling transfer and retransfer.

Confirm before orderingGenerator start interface, warm-up and cool-down logic, voltage/frequency sensing, poles, neutral design and remote status needs.
Product details
Automatic Transfer Switch Selection Guide

Confirm these requirements before choosing an ATS model

A useful ATS inquiry describes the complete power system, not only the load current. These nine items reduce revisions and help identify missing protection or controller requirements.

Source arrangement

Define utility-to-utility, utility-to-generator or another approved dual-source arrangement and identify the preferred source.

Provide the single-line diagram

Voltage and frequency

State phase-to-phase and phase-to-neutral voltage, frequency, phase sequence and acceptable source variation.

Confirm both power sources

Current and load type

Provide calculated load current, design margin and whether the load includes motors, transformers, UPS, lighting or mixed equipment.

Check the utilization category

Poles and neutral

Confirm single- or three-phase conductors, solid or switched neutral, grounding scheme and local electrical requirements.

Do not choose poles from current alone

Class and protection

Specify PC or CB class, available fault current, upstream protective devices and required short-circuit ratings.

Coordinate the complete protection system

Transfer and retransfer logic

Define source-failure delay, generator warm-up, transfer delay, normal-source return delay and generator cool-down.

Use controller-specific timing ranges

Controller functions

List voltage/frequency sensing, phase-loss detection, auto/manual modes, test function, alarms and status indication.

Match functions to operating procedure

Remote interfaces

Confirm generator dry contact, fire input, common alarm, source position outputs, remote control and communication protocol.

Provide the I/O list or BMS requirement

Installation and environment

State open or enclosed supply, mounting, cable direction, dimensions, ambient temperature, altitude, pollution and enclosure rating.

Provide panel space and destination country
ATS Controller and Transfer Logic

Configure the sequence around the actual standby source

Controller features and timing ranges vary by model. Establish the intended operating sequence first, then confirm that the selected controller provides the required inputs, outputs and adjustable settings.

A
Source acceptanceDefine undervoltage, overvoltage, underfrequency, overfrequency, phase loss and restoration limits as required.
B
Generator start and stabilizationConfirm dry-contact behavior, crank logic handled by the genset controller and source-available delay.
C
Transfer operationConfirm open-transition sequence, center-off behavior if applicable, operating time and interlocking for the exact mechanism.
D
Retransfer and cool-downKeep the load on the alternate source until normal power is stable, then allow the generator to cool before stop.
E
Remote indication and eventsMap source availability, switch position, alarms, remote test and communication points to the project I/O list.
ATS Poles, Neutral and Protection Coordination

Match the switch to the distribution system

Poles, neutral treatment and fault-current performance affect system safety and nuisance operation. The project engineer should confirm grounding and protection using the applicable local rules.

Design itemWhat must be confirmedWhy it mattersUseful project input
2-pole configurationSingle-phase conductor arrangement and whether both line and neutral are switchedDetermines isolation, conductor routing and compatibility with the grounding schemeSingle-line diagram and source wiring
3-pole configurationThree switched phase conductors with the neutral handled outside the switching mechanismCan be appropriate only when the neutral and grounding design allow a solid neutralGrounding/bonding diagram and local code
4-pole configurationThree phases plus a fully switched neutral for the specified systemMay be required for separately derived sources or particular ground-fault arrangementsGenerator bonding and neutral design
Rated operational currentContinuous load, diversity, temperature, enclosure, conductor and utilization categoryFrame size alone does not confirm suitability for every load or installation conditionLoad schedule and design current
Short-circuit withstandIcw/Icm or conditional short-circuit rating and duration for the exact PC-class modelThe ATS must coordinate with the available fault current and upstream protectionFault study and protective-device model
Breaking capacityApplicable breaking data, trip unit and settings for a CB-class arrangementProtection behavior must match system selectivity and fault-clearing requirementsProtection study and setting schedule
Transition methodOpen transition, delayed transition, center-off requirement or another specified sequenceAffects interruption, source overlap, inductive loads and operational procedureCritical-load requirement and sequence of operation
Standards and documentsApplicable IEC 60947-6-1 edition, project certificates, test reports and destination requirementsDocumentation and ratings can differ by model, production configuration and marketSpecification, country and approval list

Engineering reminder: The ATS should be selected and installed by qualified electrical personnel using the exact product documentation, system study and local electrical requirements.

Automatic Transfer Switch Applications

Define the ATS from the load continuity requirement

Different facilities can use the same basic transfer principle but require very different protection, timing, interfaces, enclosures and maintenance provisions.

01

Industrial machinery

Transfer control power or selected machine loads while accounting for motors, drives, restart logic and process interruption.

Review load type, restart sequence and utilization category
02

Commercial buildings

Support emergency distribution for lighting, pumps, communication, security and selected building systems.

Review load priority, fire interface and BMS points
03

Generator backup systems

Monitor utility power, command the generator controller and manage transfer, retransfer and cool-down timing.

Review genset start contact and neutral grounding
04

Telecom and infrastructure

Coordinate power continuity for network, signaling, communication and remote-site auxiliary loads.

Review alarms, remote monitoring and environment
05

Data and control systems

Use an ATS as one part of a wider resilience design that may also include UPS, generators and power monitoring.

Review allowable interruption and source coordination
06

OEM electrical equipment

Integrate a confirmed ATS model, controller settings, labels and wiring interface into repeatable equipment production.

Review drawings, item codes and batch documentation
Automatic Transfer Switch RFQ

Send the power-system details for an accurate quotation

Provide the available information even if the ATS model is unknown. A single-line diagram, load schedule and controller I/O list can shorten model review.

STEP 01

Describe the sources and load

Voltage, frequency, phase, normal and alternate source, load current, load type and available fault current.

STEP 02

Define switching and control

PC or CB class, poles, neutral, auto/manual mode, delays, generator start, alarms, remote I/O and communication.

STEP 03

Confirm supply details

Open or enclosed form, dimensions, quantity, destination, standards, documents, OEM labels and packaging.

Automatic transfer switch prepared for model and quality verification
Model Verification and OEM Supply

Keep every ATS order aligned with the approved specification

The quotation, drawing, nameplate, controller configuration, accessories and shipment labels should identify the same approved model and project requirements.

01
Model and rating identityVerify complete model code, rated voltage/current, poles, frequency, class and required utilization data.
02
Mechanism and interlock reviewCheck switching positions, manual operation provisions, visible assembly and model-specific interlocking.
03
Controller and I/O confirmationAlign source sensing, delays, generator contacts, alarms, status outputs and communication with the approved list.
04
Documentation and packagingPrepare required labels, drawings, datasheets, model separation and project-grouped packaging before shipment.
Automatic Transfer Switch FAQ

ATS selection questions

Use these answers to prepare the specification before requesting a model or quotation.

How do I choose an automatic transfer switch?

Start with the source arrangement, system voltage and frequency, load current and type, poles, neutral and grounding design. Then confirm PC or CB class, short-circuit coordination, controller sensing, timing, generator interfaces, communication, installation environment, standards and documentation.

What is the difference between PC class and CB class ATS?

PC class transfer switching equipment can make and withstand specified short-circuit currents but is not intended to break them, so it requires coordinated upstream protection. CB class equipment is intended to make, withstand and break short-circuit currents and includes overcurrent releases. Always use exact model data.

Should I choose a 3-pole or 4-pole ATS?

The choice depends on whether the neutral must remain solidly connected or be switched. A switched neutral may be required for separately derived sources or certain ground-fault arrangements. The system grounding design and local electrical rules should determine the pole configuration.

Can an ATS start a standby generator automatically?

A generator-oriented ATS controller can provide a dry contact or specified interface to the generator controller. Confirm contact logic, controller supply, generator warm-up, source-available sensing, retransfer delay and cool-down requirements for the exact model.

How fast should an ATS transfer?

The required transfer time depends on the load and the complete resilience design. Sensitive loads may also require a UPS. Confirm the selected ATS operating time, intentional delays, transition method and total source-restoration sequence rather than relying on one headline switching value.

Does an ATS provide short-circuit and overload protection?

It depends on the ATS class and exact construction. PC class equipment normally relies on coordinated upstream protective devices. CB class equipment includes overcurrent releases and is intended to break short-circuit currents. Verify ratings, settings and selectivity for the complete system.

What controller functions should I specify?

Common requirements include source voltage and frequency monitoring, phase-loss detection, source-failure and restoration delays, automatic and manual modes, generator start output, fire input, source-position outputs, common alarm, remote test and communication. Availability is model-specific.

Can SENTOP supply an enclosed ATS panel?

Open-device or enclosed supply can be reviewed from the project drawing, enclosure dimensions and rating, cable entry, internal protection, meters, indicators, control power, terminal arrangement, destination standards and quantity.

What information should I send for an ATS replacement?

Send the complete model and nameplate, front and rear photos, wiring diagram, voltage, frequency, current, poles, neutral arrangement, dimensions, mounting, controller terminals, upstream protection, load type and required quantity. A sample or original datasheet can improve matching.

Automatic Transfer Switch Supply Support

Send your single-line diagram, ATS model or project specification

SENTOP can review compact, molded-case, controller-equipped and generator automatic transfer switch requirements for model matching, samples, OEM equipment and bulk orders.

View Catalogue
滚动至顶部