Transfer and withstand
The non-fused PC switch compared here can make and withstand the declared short-circuit duty, but is not the fault interrupter. Coordinated protective devices clear faults.
Non-fused, switch-based comparisonTransfer switching / protection architecture
Choose the class by its short-circuit role. Then verify the protection, load duty and complete tested arrangement—not just the ampere rating or controller features.
Transfer control is a separate question.
Declared conditions must match the system.
Component certificates are not the whole proof.
Current IEC publication is not automatic local adoption.
The direct answer
PC-Class and CB-Class describe the short-circuit role of transfer switching equipment (TSE). They do not mean automatic versus manual operation.
Scope of this comparison: the PC path below is a non-fused, switch-based arrangement. Class PC also includes fuse-combination units with a fault-breaking role, so “PC never breaks a fault” is not a complete definition for every configuration.
The non-fused PC switch compared here can make and withstand the declared short-circuit duty, but is not the fault interrupter. Coordinated protective devices clear faults.
Non-fused, switch-based comparisonCB-Class TSE includes overcurrent releases and is intended to interrupt short-circuit current. Its making, breaking and any assigned short-time withstand ratings still need verification.
Fault interruption is part of the CB arrangementDefinition nuances: ABB IEC classification training (2022). Product-family examples: Schneider Electric source-changeover range. Apply the edition and exact configuration required by the project.
Keep the labels separate
A technically complete specification needs more than “automatic ATS.” Class, operating mode, utilization category and controller scope describe different things.
PC and CB describe different short-circuit roles. Class CC contactor-based equipment also exists; this guide compares PC and CB, not every class.
MTSE is manual, RTSE is remote and ATSE is automatic transfer switching equipment. The command method does not establish the fault-interruption role.
The declared category connects switching duty to the load and operating conditions. It does not replace a short-circuit or coordination review.
Source sensing, commands, timing, alarms and communications control the transfer. A controller cannot confer a class on an unverified power assembly.
The IEC record confirms that the fourth edition replaces the 2021 edition. Its scope includes manual, remote and automatic TSE, plus specified bypass/isolation, closed-transition and controller arrangements. State the edition adopted by the project and local authority; international publication does not make it legally adopted everywhere. Official IEC edition record.
Scope limit: the IEC record covers TSE at rated voltages up to 1,000 V AC or 1,500 V DC; that is not a rating assigned to every product. Class CC and controller distinctions are illustrated in Socomec’s ATS controller brochure.
Conceptual comparison
Both approaches need a verified system. The key difference is the duty assigned to the transfer equipment itself.
Non-fused PC-Class concept
CB-Class concept
Concept only—not a wiring diagram or a switching state. Protective-device locations are illustrative; the project design determines source- and load-side protection. Conductors, neutral arrangements, earthing and terminals are intentionally omitted. The two sources are not shown as permitted to operate in parallel.
| Decision point | Non-fused PC-Class TSE | CB-Class TSE |
|---|---|---|
| Fault-clearing role | Not intended to interrupt short-circuit current. | Intended to interrupt short-circuit current with overcurrent releases. |
| Typical device basis | Switch or switch-disconnector architecture. | Circuit-breaker-based architecture. |
| Critical evidence | Declared withstand/conditional ratings and associated protection. | Breaking capability, any assigned withstand duty, release settings and coordination. |
| Misleading shortcut | “There is a breaker somewhere, so the switch is protected.” | “The breaker frame is large enough, so the complete ATS is suitable.” |
| What both need | Exact configuration, load-duty review, interlocks and acceptance plan. | Exact configuration, load-duty review, interlocks and acceptance plan. |
Non-fused PC-Class application
A non-fused PC-Class switch can fit a design that deliberately assigns fault clearing to coordinated protective devices.
Switch and switch-disconnector technologies are common PC-Class implementations. The transfer equipment handles its declared normal switching duty and specified short-circuit stresses; it is not the device selected to interrupt the fault.
Do not leave the protection requirement at “upstream breaker by others.” State the device type, relevant ratings and applicable settings, and obtain the manufacturer’s coordination evidence for the offered combination.
Conditional short-circuit performance applies only with the stated protective devices and test conditions. A number in a catalogue is not an unrestricted system rating.
Check isolation needs, poles, neutral treatment, interlocks, enclosure and controller arrangement independently of the class decision.
Name who supplies, sets, verifies and records the associated protection: supplier, panel builder, designer or installer.

CB-Class application
CB-Class can fit a design that requires overcurrent releases and a fault-interruption function in the TSE.
Check breaker frames, releases, protection settings, interlocks, controller behavior, transfer sequence and configuration limitations. Coordination and selectivity remain design tasks even when the equipment includes fault-clearing devices.
Do not assume every CB-Class assembly has the same short-time withstand capability. Any assigned withstand current and duration must be checked alongside the breaking and making ratings. A settings change can alter the coordination result.
Schneider’s source-changeover family distinguishes breaker-based Class CB and switch-disconnector-based Class PC solutions. This is an architecture distinction, not evidence that either one is inherently correct for every facility.
Product-family context: Schneider source-changeover equipment. The 2021 IEC record also describes CB-type performance alignment with IEC 60947-2; use the project-required edition for the actual acceptance basis.
For derived TSE, applicable component-test evidence can cover tests already addressed by the relevant device standards. This avoids unnecessary repeat testing; it does not remove complete-TSE verification and marking. See the IEC 2026 published sample, derived-TSE definition.
Evidence that drives selection
Rated current is only one input. The fault level, clearing conditions and load behavior decide whether the proposed arrangement is suitable.
| Item to verify | Why it matters | Evidence to obtain |
|---|---|---|
| Prospective short-circuit current | Establishes fault duty at the TSE, including relevant source contributions. | Current study or calculation, source assumptions, location and revision date. |
| Protection architecture | Defines where faults are interrupted and which devices must coordinate. | One-line, device references, ratings, settings and manufacturer coordination data. |
| Utilization category and load | Matches declared switching duty to actual loads and operating frequency. | Load list, motor/transformer behavior, duty cycle and exact product category. |
| Transfer sequence | Open, delayed, closed and bypass functions change the equipment and controls. | Approved functional narrative and permissible load interruption. |
| Poles, neutral and earthing | Changes the power path and the review of source grounding. | Source topology, grounding diagram and project requirements. |
| Complete tested configuration | Individual component compliance does not prove the final TSE claim. | Manufacturer declaration, marking, manuals, wiring and configuration record. |
Short-time withstand is a manufacturer-assigned rating under stated test conditions, not a fault-breaking value. Schneider Electric: what Icw means.
A certificate labelled “CB” can refer to the IECEE CB certification scheme, not CB-Class TSE. For example, Socomec’s published ATyS a M CB Scheme certificate explicitly states equipment class PC. Read the class field rather than the certificate title.
Controls are a separate layer
Compatibility, interlocking and transfer behavior still have to be demonstrated for the complete system.
Source sensing, voltage and frequency limits, timing, generator-start commands, alarms and communications belong in the control specification. They do not show whether the power devices are intended to interrupt a short circuit.
Verify controller compatibility with the selected switching devices, position feedback, interlocks and required operating modes. Define how the arrangement responds to a protective trip and prevents inappropriate transfer or re-energization of a faulted load.
Open, delayed and closed transition are separate choices from PC or CB class. Bypass/isolation and neutral requirements also need their own review; they are not implied by the class label.
Socomec’s C25/C35 brochure lists model-dependent PC, CB and CC compatibility and specific tested combinations. It demonstrates why a controller name alone is not full-system evidence.

A six-stage selection workflow
Resolve the design basis first, then check the offered equipment against it.
Specify manual, remote or automatic operation; transfer behavior; bypass/isolation; controller scope; and acceptable load interruption.
Confirm sources, voltage, frequency, load duty, poles, neutral/earthing, fault level and protective-device locations on the current one-line.
Evaluate PC where associated protection clears faults. Evaluate CB where the TSE must include the breaker fault-interruption role.
Match devices, releases, controller, interlocks, enclosure, accessories and sequence to the documented manufacturer configuration.
Check applicable withstand/conditional ratings for PC, or breaker capability, assigned withstand duty and settings for CB. Review selectivity.
Assign functional tests, interlocking proof, settings records, alarms, documentation and operator handover before procurement closes.
Illustrative scenario / not a site design
Consider a motor and mixed auxiliary-load panel that needs automatic transfer. The load voltage alone cannot select the class.
Option A / PC-Class
A purpose-built transfer device is paired with the documented protective arrangement. The review checks declared short-circuit conditions, exact protective-device references and the utilization category for the load.
Prove the TSE + protection combinationOption B / CB-Class
A complete CB-Class TSE includes the selected breaker paths and releases. The review checks fault-interruption duty, any assigned withstand rating, interlocking, controller behavior and responsibility for settings.
Prove the complete TSE + settingsBoth may be candidates only if their respective arrangements are verified. This example gives no model selection, current rating, universal fault threshold or cost ranking.
Common selection errors
It describes control. Request the IEC class marking and supporting TSE documentation separately.
The switch is not the fault interrupter. Check the associated protection and all declared coordination conditions; do not generalize this to fuse-combination units.
For CB, obtain release details, breaking capability, any assigned withstand duty, settings, interlocks and complete TSE evidence.
They do not establish the complete source-changeover claim. Match the actual assembled configuration to manufacturer evidence.
It does not replace utilization category, load behavior, neutral design or an approved transfer narrative.
State the required edition and applicable national adoption. A newer publication does not automatically invalidate every earlier project specification.
Buyer’s evidence pack
Ask for a documented arrangement with clear responsibilities, not a loosely defined set of components.
| Include in the RFQ | What the supplier and project team must resolve |
|---|---|
| 01 Required standard edition | IEC 60947-6-1:2026 or the formally adopted project edition, plus applicable local requirements. |
| 02 Operating designation | MTSE, RTSE or ATSE; controller scope, sensing, alarms, communications and transfer/retransfer logic. |
| 03 Class and design rationale | PC or CB requirement, where faults are cleared and the short-circuit data supporting the choice. |
| 04 Electrical and load data | Voltage, frequency, current, poles, neutral/earthing, load duty, fault level and utilization category. |
| 05 Protection evidence | Exact associated protection and coordination for PC; breaker/release, ratings, settings and coordination for CB. |
| 06 Complete assembly evidence | Type-test declaration, class marking, wiring, interlocks, enclosure/IP needs, accessories and configuration limits. |
| 07 Acceptance and handover | Agreed tests, settings records, as-builts, manuals, training, warranty responsibilities and maintenance information. |
Verification and handover
Commissioning verifies the specified functions in the installation. It does not substitute for missing manufacturer type-test evidence.
Assign qualified personnel to the approved acceptance plan. Record who owns wiring and interlocking checks, source sensing, transfer/retransfer behavior, protection settings, alarms and communications. Use the exact manufacturer instructions and project criteria.
Do not infer safety, isolation or compliance from any photograph on this page. Installation, testing and maintenance require the applicable qualified-person procedures.

Frequently asked questions
Keep the class, protection scheme and evidence requirements connected.
In the non-fused, switch-based PC arrangements compared here, the transfer switch makes and withstands the declared fault duty while coordinated protective devices interrupt the fault. CB-Class TSE includes the fault-interruption function. Class PC also includes fuse-combination units with a fault-breaking role, so the non-fused comparison is not a universal definition. Verify the complete arrangement, applicable edition and declared ratings; CB short-time withstand depends on an assigned manufacturer rating.
Often, but do not use the device label as the proof. Manufacturers commonly describe switch-disconnector-based source-changeover equipment as PC-Class. The correct decision still requires the product's IEC 60947-6-1 class marking, utilization category, short-circuit coordination data, and the exact associated protective-device arrangement.
No. ATSE describes automatic transfer operation, not an exhaustive list of short-circuit classes. Class CC contactor-based equipment also exists. This guide compares PC-Class and CB-Class; neither the automatic label nor controller compatibility proves the class of the complete transfer assembly. Confirm the marking and documentation for the exact configuration.
Possibly, but only within the manufacturer's declared short-circuit ratings and stated protective-device coordination. High prospective fault current is not an automatic rejection or approval. Obtain the exact TSE coordination data, verify the protective devices and settings, and have the qualified project team confirm applicability. A conditional rating is not a standalone fault-interruption rating.
No. CB-Class equipment includes the fault-interruption and overcurrent-release function, but breaker ratings, release settings, source contributions, discrimination/selectivity, interlocking, and the complete system still need review. The equipment class is one input to a coordinated protection design, not a substitute for it.
As of this guide's publication, IEC 60947-6-1:2026 is the fourth edition and replaced the 2021 edition on 2 April 2026. The RFQ should state the edition required by the project and any national adoption or authority requirement. Do not assume a standard is legally adopted everywhere simply because it is current internationally.
Only if the resulting configuration is documented, marked, and type-tested as complete transfer switching equipment to the applicable requirements. The IEC 2026 scope excludes configurations not fully manufacturer type-tested or marked as a complete transfer switch. Request evidence for the exact arrangement, not only component certificates. Applicable component tests may support derived-TSE verification where the standard allows; complete-configuration requirements still apply.
Request the marked TSE data, one-line and wiring diagrams, protective-device and controller settings, coordination evidence, test results, interlocking/transfer test records, manuals, as-builts, training records, and maintenance information. These records let the operator understand both the transfer function and the protective architecture after commissioning.
Technical references
The standard edition, application literature and configuration-specific records serve different purposes. Check which one supports each claim.
A defensible specification starts with the system
Share source data, fault-current information, load duty, transfer sequence and the required standard edition. Ask the qualified designer and supplier to confirm the complete PC-Class or CB-Class arrangement before procurement.
Product and project enquiry
Share the model, ratings, quantity and destination you already know. SENTOP will review the remaining selection details with you.
SENTOP Team
Typically replies within minutes
Do you want to learn more about our products or services?
Contact Us
🟢 Online | Privacy policy
Contact Us