The controller evaluates a defined acceptance window
In a typical utility-generator system, the automatic controls evaluate the preferred source and determine whether the alternate source is ready. Depending on the selected model and options, monitored conditions can include undervoltage, overvoltage, underfrequency, overfrequency, phase loss, phase rotation or voltage imbalance. Confirm which functions are actually present, enabled and applied to each source.
When the connected source becomes unacceptable for the configured period, the control sequence can request an alternate source. If that source is a generator, the engine must start and establish the required electrical conditions before load transfer is allowed. A running engine or a single meter reading is therefore not the same as an accepted source.
While the load uses the alternate supply, the control system can continue evaluating the preferred source for restoration. It must then apply the configured return policy. “Normal” is a source role in the design—not a universal promise that utility is always preferred.
Where provided, different acceptance and rejection thresholds create hysteresis: a margin that helps avoid repeated state changes near one boundary. This is different from waiting for a timer.
A delay can require a condition to persist before the next action. Verify nominal voltage/frequency, sensing connections, thresholds and delay settings against the approved design—not another ATS model.