DC Isolator Switches for Safe, Visible Circuit Separation

Select a DC isolator or switch-disconnector from the maximum system voltage, operational current, required load-switching duty, pole arrangement, installation method and environmental conditions. SENTOP supports photovoltaic, battery, industrial DC, OEM panel and bulk-supply requirements.

Tinjau Faktor-faktor Seleksi
TeganganMaximum operating voltage and source open-circuit voltage
terbaruOperational current, load profile and applicable derating
fungsiIsolation only or declared load-switching capability
PolandiaRequired switched conductors and series-contact diagram
InstalasiDIN rail, panel, enclosure or equipment integration

Function Before Product

Separate a DC circuit, then confirm whether it must break load current

A DC isolator provides a defined isolation function so equipment can be separated from an energized source for maintenance. A switch-disconnector combines isolation with a declared making and breaking capability under specified utilization conditions.

The two terms are often used loosely in the market, but their duties are not interchangeable. The exact product data must show whether the device may operate under load, at what DC voltage and current, and with which contact wiring.

01

Fungsi isolasi

Provides a defined open state for maintenance when installed and operated according to the product instructions and system procedure.

02

Peralihan beban

Requires a switch-disconnector with a declared DC utilization category and operational current for the actual voltage and circuit.

03

Gangguan kesalahan

A DC isolator is not automatically an overcurrent protective device. Short-circuit protection must be provided and coordinated separately unless expressly integrated.

04

Visible operating state

Rotary handles, position indication and lockable OFF arrangements can support safe operating procedures, subject to the exact model design.

Maintenance separationPemutus DCChosen primarily for isolation. Do not assume it can interrupt normal load current unless the product has a declared switching duty.
Isolation plus operationSakelar Pemutus DCProvides isolation and declared making/breaking performance for specified voltage, current and utilization category.
Perlindungan arus berlebihPemutus Sirkuit DCProtects against defined overload and short-circuit conditions while also providing switching functions within its declared ratings.
Frequent or remote controlKontaktor DCUsed for electrically operated switching; isolation, protection and emergency functions still require system-level coordination.

DC Isolator Selection Process

Match the device to the real DC circuit

A current value on the front label is not enough. DC arc extinction depends on voltage, current, contact spacing, contact stages and the manufacturer's tested wiring arrangement.

Basis seleksiMaximum DC voltage + operational current + utilization category + switched conductors + series-contact diagram + installation environment + backup protection
01

Identify the DC source

State whether the circuit is photovoltaic, battery, rectifier, telecom, transport or industrial DC, because voltage behavior and fault energy differ.

02

Use maximum voltage

For PV, consider maximum array open-circuit voltage at the minimum design temperature. For other systems, use the highest credible operating and charging voltage.

03

Define switching duty

Confirm whether the device is operated only after current is removed or must make and break load current under a declared category such as DC-PV2.

04

Calculate operational current

Include continuous load, PV string or array current, overload expectations, enclosure temperature, grouping and model-specific derating.

05

Confirm poles and contact stages

Specify which positive and negative conductors are switched and follow the exact series or parallel contact wiring shown for the selected model.

06

Coordinate fault protection

Verify prospective short-circuit current, upstream fuse or breaker, conditional short-circuit data and required protection of conductors and equipment.

07

Choose the installation format

Match DIN rail, panel mounting, door coupling, enclosed outdoor mounting, equipment integration, terminal access and available space.

08

Verify environment and approvals

Review IP rating, temperature, altitude, UV exposure, pollution degree, lockability, terminals, standards and target-market documentation.

DC Isolator Product Directions

Choose the format from the installation and switching duty

These directions organize an enquiry. Final performance must be confirmed from the exact model datasheet, wiring diagram, markings and certificate scope.

01Modular rotary DC isolator switch for DIN rail installation
Instalasi kabinet kompak

DIN Rail DC Switch-Disconnector

A compact direction for combiner boxes, inverter input cabinets and industrial DC panels where accessible modular mounting is required.

Konfirmasi: maximum voltage, operational current, poles, series-contact wiring, utilization category, module width and terminals.
02Front operated multipole DC isolator switch with rotary handle
Front-operated separation

Panel-Mounted Rotary DC Isolator

A front-operated direction for machinery, electrical enclosures and local disconnection points where clear ON/OFF operation is important.

Konfirmasi: mounting cutout, shaft or handle arrangement, poles, padlocking, door interlock, terminals and enclosure design.
03Lockable red and yellow DC isolator switch for local panel operation
Lockable local control

Padlockable DC Isolation Switch

A maintenance-focused direction where a clear OFF position and provision for lockout are required in the operating procedure.

Konfirmasi: lock positions, handle accessibility, enclosure rating, utilization category, electrical life and isolation procedure.
04Four-pole industrial rotary DC isolator switch
Multi-pole industrial duty

Multi-Pole DC Isolator Assembly

A four-pole direction for higher-voltage contact series arrangements, multiple conductors or project-specific industrial switching schemes.

Konfirmasi: exact terminal map, contacts in series, polarity, conductor routing, voltage per path, current and protective-device coordination.

Penting: similar-looking isolators can have different voltage tables, wiring diagrams and load-breaking duties. Order from the exact model code and approved documentation, not from appearance alone.

DC Switching Data

The ratings that determine usable performance

DC current does not pass through a natural current zero on every half cycle as AC does. Contact opening, arc length and the complete contact path are therefore central to safe switching.

UeTegangan operasional

Maximum declared DC voltage

Use the product's rated operational voltage for the exact contact arrangement and utilization category.

PV maximum open-circuit voltageBattery charge voltageVoltage per switched path
IeOperational current

Current under stated conditions

Operational current depends on the switching category, voltage, ambient conditions and product construction.

Arus beban terus menerusPV design currentEnclosure and thermal derating
DCKategori pemanfaatan

Declared load-switching duty

Categories such as DC-PV2 define application-specific operating conditions. A thermal current marking alone does not prove load-break capacity.

Make and break dutyApplication and time constantElectrical operating cycles
4PPengaturan kontak

Poles and series contacts

Multiple contacts may be placed in series to interrupt a higher DC voltage. Wiring must follow the exact manufacturer diagram.

Positive and negative conductorsSeries versus parallel pathTerminal numbering and polarity

Also verify rated insulation voltage, impulse withstand voltage, conditional short-circuit current, required backup device, mechanical/electrical endurance, terminal capacity and temperature limits for the exact model.

Standar dan Dokumentasi

Confirm the standard scope against the aplikasi lengkap

A standard number on a catalogue does not automatically confirm every voltage, current, utilization category, enclosure or target-market requirement.

SWITCHING DEVICE

IEC 60947-3

Covers low-voltage switches, disconnectors, switch-disconnectors and fuse-combination units. Review the exact device function, utilization category and declared ratings.

ATURAN UMUM

IEC 60947-1

Provides general rules for low-voltage switchgear and controlgear, including referenced definitions, characteristics and test conditions used by product standards.

PV ARRAY DESIGN

IEC 62548-1

Addresses photovoltaic array design requirements including DC wiring, switching, earthing and isolation provisions within the complete PV array.

PV INSTALLATION

IEC 60364-7-712

Applies to low-voltage photovoltaic power-supply installations. Device selection must fit the installation architecture and local rules.

MODEL EVIDENCE

Datasheet and test scope

Verify model code, voltage/current table, wiring diagram, utilization category, certificate owner, report scope, markings and production identity.

DESTINATION MARKET

Local code and approvals

Confirm required national standards, installer rules, labels, language, enclosure, disconnect location and authority acceptance before ordering.

Enclosed DC isolator installed beside a photovoltaic inverter
Local DC isolation near PV equipmentThe isolator location, enclosure, cable entry and operating access must support the installation and maintenance plan.

Petunjuk Aplikasi

Place isolation where the system and service procedure need it

The device is one part of the DC system. Cable protection, overcurrent protection, earthing, inverter or battery instructions, emergency procedures and access must be coordinated with it.

PV array and combiner boxMatch maximum array voltage, design current, polarity, enclosure, string protection and switching location.
PV inverter inputCoordinate the external or integrated isolator with inverter instructions, MPPT inputs and source arrangement.
Battery and energy storageConfirm bidirectional current, maximum charge voltage, prospective fault current, pre-charge and system-specific switching duty.
Industrial DC equipmentReview load type, time constant, motor or inductive duty, frequent-operation needs and maintenance separation.
Telecom and control powerCoordinate voltage, polarity, redundant feeds, remote monitoring and continuity requirements.
Penutup listrik OEMIntegrate handle, shaft, door coupling, terminals, labels, clearances and approved operating instructions.

Siapkan Pertanyaan yang Bermanfaat

Three items make DC isolator matching faster

Send the electrical source data, switching requirement and installation conditions together. Photos of an existing label and terminal diagram are useful for replacements.

01 / LISTRIK

Source and ratings

Application, nominal and maximum DC voltage, operational current, number of strings or feeds, poles, prospective fault current and existing protection.

02 / SWITCHING

Fungsi yang dibutuhkan

Isolation only or load breaking, operating frequency, utilization category, conductor arrangement, terminal diagram and lockout requirement.

03 / PROJECT

Installation and supply

DIN rail, panel or enclosure, IP rating, temperature, cable size, dimensions, approvals, quantity, destination, packaging and delivery schedule.

Instalasi dan operasi

Control the DC arc with the correct device and wiring

Installation, testing and maintenance should be completed by qualified people using the product instructions and site safety procedure.

Do not operate an isolation-only device under load. Load switching is permitted only where the exact switch-disconnector has the required DC utilization category and ratings for the circuit.
Follow the terminal diagramDo not improvise series or parallel contact bridges. One changed link can alter the voltage capability and arc path.
Check polarity and directionObserve all line/load, positive/negative or directional markings when the design requires them.
Torque and conductor preparationUse the declared cable range, ferrules or lugs where required, strip length and terminal torque.
Coordinate backup protectionInstall the declared fuse or circuit breaker arrangement and verify it against the available fault current.
Lindungi wadah tersebutMaintain clearances, IP sealing, cable glands, ventilation, temperature limits, UV resistance and drain paths.
Verify isolation on both sidesPV and battery circuits may remain energized from the source side. Test for absence of voltage using the approved procedure.
Inspect for heatingLook for discoloration, loose terminals, cracked enclosures, moisture, abnormal odor, stiff operation or damaged labels.
Replace by exact dutyMatch voltage, current, category, poles, terminal map, dimensions and approvals rather than selecting by handle appearance.
Industrial multi-pole DC isolator switch for OEM electrical assemblies
OEM supply starts with an approved electrical configuration, wiring diagram and sample rather than a generic housing reference.

OEM, Replacement and Bulk Supply

Keep the approved electrical identity konsisten

SENTOP can support model review, samples, eligible private-label requirements, packaging and repeat procurement for distributors, panel builders, inverter suppliers and equipment manufacturers.

01
Model and replacement reviewMatch by label photo, voltage/current table, utilization category, terminal diagram, dimensions, handle and certificates.
02
Persetujuan sampel dan dokumenReview operating feel, terminals, markings, wiring, temperature data, test scope and installation instructions before bulk production.
03
Persyaratan OEM dan pengemasanDefine eligible artwork, model code, label data, barcode, instructions, carton, traceability and target-market information.
04
Controlled repeat supplyUse the approved specification as the baseline and document technical, component, marking or packaging changes before reorder.

DC Isolator Switch FAQ

Buyer and installation questions

Use these answers to define the circuit before requesting an exact model, replacement or OEM configuration.

Apa itu saklar isolator DC?

A DC isolator is a manually operated device used to separate a DC circuit for maintenance. If the product is also a switch-disconnector, it may make and break specified load current under its declared DC utilization category and ratings.

Is a DC isolator the same as a DC circuit breaker?

No. An isolator provides circuit separation and may have declared load-switching capability, while a DC circuit breaker is intended to interrupt specified overcurrent or short-circuit conditions. The isolator normally requires coordinated upstream protection.

Can every DC isolator switch current under load?

No. Load interruption is allowed only when the exact device is declared as a switch-disconnector for the applicable DC voltage, current, utilization category, contact arrangement and operating conditions.

What does DC-PV2 mean?

DC-PV2 is a photovoltaic DC utilization category used for switch-disconnectors intended to make and break circuits where substantial overcurrents may occur. Confirm the exact product's declared voltage, current and test scope.

How do I choose the voltage rating for a PV DC isolator?

Use the maximum array open-circuit voltage under the minimum design temperature, not only the nominal operating voltage. Then confirm that value against the exact contact wiring and rated operational voltage table.

How do I choose the current rating?

Determine the circuit design current from the source and load, then apply the relevant PV, installation, enclosure, ambient-temperature and manufacturer derating factors. Check operational current at the selected voltage and category.

Why are multiple poles or series contacts used in DC isolators?

Placing contacts in series increases the total open contact distance and can help extinguish a higher-voltage DC arc. The terminal links and conductor path must follow the exact approved wiring diagram.

Can an AC isolator be used on a DC circuit?

Only when the exact product has a declared DC rating for the required voltage, current, duty and wiring arrangement. An AC-only rating must not be assumed suitable because DC arcs behave differently.

Where should a PV DC isolator be installed?

The location depends on the PV array and inverter design, local installation rules, accessibility and equipment instructions. It may be near the array, combiner, inverter or integrated into equipment, with suitable enclosure and cable routing.

When should a DC isolator be inspected or replaced?

Inspect according to the installation and maintenance plan and after abnormal events. Replace a device with heat damage, loose or damaged terminals, moisture ingress, cracked housing, unreliable operation, unreadable markings or performance outside the approved model condition.

Can SENTOP support OEM and bulk DC isolator orders?

Eligible configurations can be reviewed for model matching, samples, labels, packaging, instructions, terminal arrangements, enclosure integration and repeat supply. Feasibility and approval scope are confirmed for the requested model and destination.

DC Isolation Supply Support

Send the maximum DC voltage, current and contact diagram

SENTOP can review DC isolator and switch-disconnector requirements for photovoltaic systems, battery equipment, industrial DC panels, replacements, samples, OEM assemblies and bulk orders.